Lightning protection pillar insulator (FEG-12/5)

Collect
商品说明

purpose

A protective device for preventing lightning strikes and wire breakage of overhead insulated conductors, as well as for electrical testing and temporary grounding during maintenance and construction, suitable for copper and aluminum overhead insulated conductors.

● Specifications and technical parameters

model

Wire cross-sectional range (mm ²)

remarks

FDL-50/240

50-240

Puncture type

FDL-50/240B

50-240

Non puncture type

● Performance parameters

1. Lightning full wave impulse withstand voltage (peak) kV: 100

2. 1-minute power frequency withstand voltage (effective value) kV: 50

3. Power frequency arc current (effective value) kA: 12.5

4. Rated bending withstand load: 5kN

5. Minimum nominal creepage distance: 360mm

6. The puncture site is coated with a unique waterproof insulation paste

● Installation instructions

Align the wire clamping slot of this product with the parallel direction of the conductor and install it on the cross arm. Tighten the steel foot nut, which is the same as the traditional installation method of insulators; Turn the ignition rod towards the load side.

◆ Puncture type thread clamping method:

1. The tightening method of aluminum alloy torque nut: parallel the insulated wire into the wire clamp groove, first tighten the torque nut by hand, then alternately and evenly tighten it with a socket wrench until the top of the torque nut falls off, and then assemble the insulation sheath on the wire clamp fixture.

2. The tightening method of ordinary nuts: Set the torque value of the torque wrench according to the wire section and weather temperature: 20-35NM. Use the torque wrench to alternately and symmetrically tighten the two pressure nuts. When the wrench reaches the set torque value, tighten the backup nut to prevent the pressure nut from loosening. Then assemble the insulation sheath on the wire clamp.

Non puncture clamping method:

Peel off the insulated wire by about 65-80mm and wrap it with aluminum tape embedded in the wire clamp fixture. Use a wrench to tighten the clamping nut and drive the pressure block seat to tighten the wire. Then assemble the insulation sheath on the wire clamp fixture.


The company actively responded to the "the Belt and Road" national policy and built an international marketing network. This product has obtained international certifications such as CE in Europe, GOST in Russia, SABS in South Africa, and has been recognized by international power standards such as ASTM in the United States and IEC in the International Electrotechnical Commission. The product is popular in more than 20 countries and regions including Europe, Pakistan, Bangladesh, the Philippines, Maldives, Ecuador, Peru, South Africa, etc.